Boiler Explosion - Locomotive Boiler Explosions in The UK

Locomotive Boiler Explosions in The UK

Hewison (1983) gives a comprehensive account of British boiler explosions, listing 137 between 1815 and 1962. It is noteworthy that 122 of these were in the 19th century and only 15 in the 20th century.

Boiler explosions generally fell into two categories. The first is the breakage of the boiler barrel itself, through weakness/damage or excessive internal pressure, resulting in sudden discharge of steam over a wide area. Stress corrosion cracking at the lap joints was a common cause of early boiler explosions, probably caused by caustic embrittlement. The water used in boilers was not often closely controlled, and if acidic, could corrode the wrought iron boiler plates. Galvanic corrosion was an additional problem where copper and iron were in contact. Boiler plates have been thrown up to a quarter of a mile (Hewison, Rolt). The second type is the collapse of the firebox under steam pressure from the adjoining boiler, releasing flames and hot gases into the cab. Improved design and maintenance almost totally eliminated the first type, but the second type is always possible if the engineer and fireman do not maintain the water level in the boiler.

Boiler barrels could explode if the internal pressure became too high. To prevent this, safety valves were installed to release the pressure at a set level. Early examples were spring-loaded, but John Ramsbottom invented a tamper-proof valve which was universally adopted. The other common cause of explosions was internal corrosion which weakened the boiler barrel so that it could not withstand normal operating pressure. In particular, grooves could occur along horizontal seams (lap joints) below water level. Dozens of explosions resulted, but were eliminated by 1900 by the adoption of butt joints, plus improved maintenance schedules and regular hydraulic testing.

Fireboxes were generally made of copper, though later locomotives had steel fireboxes. They were held to the outer part of the boiler by stays (numerous small supports). Parts of the firebox in contact with full steam pressure have to be kept covered with water, to stop them overheating and weakening. The usual cause of firebox collapses is that the boiler water level falls too low and the top of the firebox (crown sheet) becomes uncovered and overheats. This occurs if the fireman has failed to maintain water level or the level indicator (gauge glass) is faulty. A less common reason is breakage of large numbers of stays, due to corrosion or unsuitable material.

Throughout the 20th century, two boiler barrel failures and thirteen firebox collapses occurred in the UK. The boiler barrel failures occurred at Cardiff in 1909 and Buxton in 1921; both were caused by misassembly of the safety valves causing the boilers to exceed their design pressures. Of the 13 firebox collapses, four were due to broken stays, one to scale buildup on the firebox, and the rest were due to low water level.

Read more about this topic:  Boiler Explosion

Famous quotes containing the words locomotive and/or explosions:

    Hereditary property sophisticates the mind, and the unfortunate victims to it ... swathed from their birth, seldom exert the locomotive faculty of body or mind; and, thus viewing every thing through one medium, and that a false one, they are unable to discern in what true merit and happiness consist.
    Mary Wollstonecraft (1759–1797)

    Our Lamaze instructor . . . assured our class . . . that our cervix muscles would become “naturally numb” as they swelled and stretched, and deep breathing would turn the final explosions of pain into “manageable discomfort.” This descriptions turned out to be as accurate as, say a steward advising passengers aboard the Titanic to prepare for a brisk but bracing swim.
    Mary Kay Blakely (20th century)