Certification Listing - Example of Fire Door Test

Example of Fire Door Test

The following pictures illustrate an example of a successful fire test that led to a UL listing or a three hour fire protection rating. The entire assembly is exposed to a fire for the specified amount of time per the objective of the test. Following this heat exposure, a hose stream is applied to the door. Fire doors and fire dampers are derated from the fire barriers they are in. In this case, a 3 hour rated door is acceptable for use in up to a 4 hour wall. Because it goes into a 4 hour wall, it received a 45PSI (31N/cm²) hose stream test.

  • Fire door listing drawing

  • Fully built fire separation with double door.

  • Test sample immediately after a 3 hour fire exposure.

  • 45 PSI hose stream test following fire.