Wiegand Interface - Physical Layer

Physical Layer

The Wiegand interface uses three wires, one of which is a common ground and two of which are data transmission wires usually called DATA0 and DATA1, alternately labeled 'D0' and 'D1' or 'Data Low' and 'Data High'. When no data is being sent both DATA0 and DATA1 are pulled up to the 'high' voltage level - usually +5 VDC. When a 0 is sent the DATA0 wire is pulled to a low voltage while the DATA1 wire stays at a high voltage. When a 1 is sent the DATA1 wire is pulled to a low voltage while DATA0 stays at a high voltage.

A high voltage level of +5VDC is used to accommodate for long cable runs (most reader manufacturers publish a maximum of 500 feet) from door readers to the associated access control panel typically located in a secure closet.

Read more about this topic:  Wiegand Interface

Famous quotes containing the words physical and/or layer:

    But alas! I never could keep a promise. I do not blame myself for this weakness, because the fault must lie in my physical organization. It is likely that such a very liberal amount of space was given to the organ which enables me to make promises, that the organ which should enable me to keep them was crowded out. But I grieve not. I like no half-way things. I had rather have one faculty nobly developed than two faculties of mere ordinary capacity.