SCSI Enclosure Services - SES Element Thresholds

SES Element Thresholds

Some SES elements, such as voltage sensors, current sensors, and temperature sensors, have a thresholding function. This allows an enclosure to detect and report unacceptable environmental conditions. The SCSI standard allows for two different threshold levels, noncritical (warning) and critical. Also, each threshold has a minimum and maximum value. So for example the threshold values for the 12 volt power-supply could be set as follows:

  • Minimum critical - 10.8 volts
  • Minimum noncritical - 11.4 volts
  • Maximum noncritical - 12.6 volts
  • Maximum critical - 13.2 volts

Threshold values are set by a Send Diagnostic command to the Threshold Out diagnostic page (05h). Threshold values can be interrogated by a Receive Diagnostic Results command to the Threshold In diagnostic page (05h) with the PCV bit set to one.

Read more about this topic:  SCSI Enclosure Services

Famous quotes containing the words ses and/or element:

    Et Saint Apollinaire, raide et ascétique,
    Vieille usine désaffectée de Dieu, tient encore
    Dans ses pierres éecroulantes la forme précise de Byzance.
    —T.S. (Thomas Stearns)

    All forms of beauty, like all possible phenomena, contain an element of the eternal and an element of the transitory—of the absolute and of the particular. Absolute and eternal beauty does not exist, or rather it is only an abstraction creamed from the general surface of different beauties. The particular element in each manifestation comes from the emotions: and just as we have our own particular emotions, so we have our own beauty.