Operation

Each closed-head sprinkler is held closed by either a heat-sensitive glass bulb (see below) or a two-part metal link held together with fusible alloy such as Wood's metal and other alloys with similar compositions. The glass bulb or link applies pressure to a pip cap which acts as a plug which prevents water from flowing until the ambient temperature around the sprinkler reaches the design activation temperature of the individual sprinkler. Because each sprinkler activates independently when the predetermined heat level is reached, the number of sprinklers that operate is limited to only those near the fire, thereby maximizing the available water pressure over the point of fire origin.

The bulb breaks as a result of the thermal expansion of the liquid inside the bulb. The time it takes before a bulb breaks is dependent on the temperature. Below the design temperature, it does not break, and above the design temperature, it takes less time for higher temperatures. The response time is expressed as a response time index (RTI), which typically has values between 35 and 250 m½s½, where a low value indicates a fast response. Under standard testing procedures (135 °C air at a velocity of 2.5 m/s), a 68 °C sprinkler bulb will break within 7 to 33 seconds, depending on the RTI. The RTI can also be specified in imperial units, where 1 ft½s½ is equivalent to 0.55 m½s½. The sensitivity of a sprinkler can be negatively affected if the thermal element has been painted.

Maximum Ceiling Temperature Temperature Rating Temperature Classification Color Code (with Fusible Link) Glass Bulb Color
100°F / 38°C 135-170°F / 57-77°C Ordinary Uncolored or Black Orange (135°F) or Red (155°F)
150°F / 66°C 175-225°F / 79-107°C Intermediate White Yellow (175°F) or Green (200°F)
225°F / 107°C 250-300°F / 121-149°C High Blue Blue
300°F / 149°C 325-375°F / 163-191°C Extra High Red Purple
375°F / 191°C 400-475°F / 204-246°C Very Extra High Green Black
475°F / 246°C 500-575°F / 260-302°C Ultra High Orange Black
625°F / 329°C 650°F / 343°C Ultra High Orange Black

From Table 6.2.5.1 NFPA13 2007 Edition indicates the maximum ceiling temperature, nominal operating temperature of the sprinkler, color of the bulb or link and the temperature classification.

Read more about this topic:  Fire Sprinkler

Famous quotes containing the word operation:

    Waiting for the race to become official, he began to feel as if he had as much effect on the final outcome of the operation as a single piece of a jumbo jigsaw puzzle has to its predetermined final design. Only the addition of the missing fragments of the puzzle would reveal if the picture was as he guessed it would be.
    Stanley Kubrick (b. 1928)

    You may read any quantity of books, and you may almost as ignorant as you were at starting, if you don’t have, at the back of your minds, the change for words in definite images which can only be acquired through the operation of your observing faculties on the phenomena of nature.
    Thomas Henry Huxley (1825–95)

    It is critical vision alone which can mitigate the unimpeded operation of the automatic.
    Marshall McLuhan (1911–1980)