Simulation-based Energy Audit Procedure For Non-residential Buildings

A complete audit procedure, very similar to the ones proposed by ASHRAE and Krarti (2000), has been proposed in the frame of the AUDITAC and HARMONAC projects to help in the implementation of the EPB (“Energy Performance of Buildings”) directive in Europe and to fit to the current European market.

The following procedure proposes to make an intensive use of modern BES tools at each step of the audit process, from benchmarking to detailed audit and financial study:

  • Benchmarking stage : While normalization is required to allow comparison between data recorded on the studied installation and reference values deduced from case studies or statistics. The use of simulation models, to perform a code-compliant simulation of the installation under study, allows to assess directly the studied installation, without any normalization needed. Indeed, applying a simulation-based benchmarking tool allows an individual normalization and allows avoiding size and climate normalization.
  • Preliminary audit stage: Global monthly consumptions are generally insufficient to allow an accurate understanding of the building’s behaviour. Even if the analysis of the energy bills does not allow identifying with accuracy the different energy consumers present in the facility, the consumption records can be used to calibrate building and system simulation models. To assess the existing system and to simulate correctly the building’s thermal behaviour, the simulation model has to be calibrated on the studied installation. The iterations needed to perform the calibration of the model can also be fully integrated in the audit process and help in identifying required measurements and critical issues.
  • Detailed audit stage: At this stage, on-site measurements, sub-metering and monitoring data are used to refine the calibration of the BES tool. Extensive attention is given to understanding not only the operating characteristics of all energy consuming systems, but also situations that cause load profile variations on short and longer term bases (e.g. daily, weekly, monthly, annual). When the calibration criteria is satisfied, the savings related to the selected ECOs/ECMs can be quantified.
  • Investment-grade audit stage: At this stage, the results provided by the calibrated BES tool can be used to assess the selected ECOs/ECMs and orient the detailed engineering study.

Read more about this topic:  Energy Audit