Reactive Power Control
Transmission connected generators are generally required to support reactive power flow. For example on the Great Britain transmission system generators are required by the Grid Code Requirements to supply their rated power between the limits of 0.85 power factor lagging and 0.90 power factor leading at the designated terminals. The system operator will perform switching actions to maintain a secure and economical voltage profile while maintaining a reactive power balance equation:
Generator_MVARs + System_gain + Shunt_capacitors = MVAR_Demand + Reactive_losses + Shunt_reactors
The ‘System gain’ is an important source of reactive power in the above power balance equation, which is generated by the capacitive nature of the transmission network itself. By making decisive switching actions in the early morning before the demand increases, the system gain can be maximized early on, helping to secure the system for the whole day.
To balance the equation some pre-fault reactive generator use will be required. Other sources of reactive power that will also be used include shunt capacitors, shunt reactors, Static VAR Compensators and voltage control circuits.
Read more about this topic: AC Power
Famous quotes containing the words power and/or control:
“La foi consiste à croire ce que la raison ne croit pas ... Il ne suffit pas quune chose soit possible pour la croire. Faith consists in believing when it is beyond the power of reason to believe ... It is not enough that a thing be possible for it to be believed.”
—Voltaire [François Marie Arouet] (16941778)
“There is one thing you and I as parents cannot do, not do we want to do if we really think about it, and thats control our childrens willthat spirit that lets them be themselves apart from you and me. They are not ours to possess, control, manipulate, or even to make mind.”
—Barbara Coloroso (20th century)