Reactive Power Control
Transmission connected generators are generally required to support reactive power flow. For example on the Great Britain transmission system generators are required by the Grid Code Requirements to supply their rated power between the limits of 0.85 power factor lagging and 0.90 power factor leading at the designated terminals. The system operator will perform switching actions to maintain a secure and economical voltage profile while maintaining a reactive power balance equation:
Generator_MVARs + System_gain + Shunt_capacitors = MVAR_Demand + Reactive_losses + Shunt_reactors
The ‘System gain’ is an important source of reactive power in the above power balance equation, which is generated by the capacitive nature of the transmission network itself. By making decisive switching actions in the early morning before the demand increases, the system gain can be maximized early on, helping to secure the system for the whole day.
To balance the equation some pre-fault reactive generator use will be required. Other sources of reactive power that will also be used include shunt capacitors, shunt reactors, Static VAR Compensators and voltage control circuits.
Read more about this topic: AC Power
Famous quotes containing the words power and/or control:
“Oh, London is a mans town, theres power in the air;
And Paris is a womans town, with flowers in her hair;
And its sweet to dream in Venice, and its great to study Rome;
But when it comes to living, there is no place like home.”
—Henry Van Dyke (18521933)
“Magic is the envelopment and coercion of the objective world by the ego; it is a dynamic subjectivism. Religion is the coercion of the ego by gods and spirits who are objectively conceived beings in control of nature and man.”
—Richard Chase (b. 1914)