AC Power - Reactive Power Control

Reactive Power Control

Transmission connected generators are generally required to support reactive power flow. For example on the Great Britain transmission system generators are required by the Grid Code Requirements to supply their rated power between the limits of 0.85 power factor lagging and 0.90 power factor leading at the designated terminals. The system operator will perform switching actions to maintain a secure and economical voltage profile while maintaining a reactive power balance equation:

Generator_MVARs + System_gain + Shunt_capacitors = MVAR_Demand + Reactive_losses + Shunt_reactors

The ‘System gain’ is an important source of reactive power in the above power balance equation, which is generated by the capacitive nature of the transmission network itself. By making decisive switching actions in the early morning before the demand increases, the system gain can be maximized early on, helping to secure the system for the whole day.

To balance the equation some pre-fault reactive generator use will be required. Other sources of reactive power that will also be used include shunt capacitors, shunt reactors, Static VAR Compensators and voltage control circuits.

Read more about this topic:  AC Power

Famous quotes containing the words power and/or control:

    The interest in life does not lie in what people do, nor even in their relations to each other, but largely in the power to communicate with a third party, antagonistic, enigmatic, yet perhaps persuadable, which one may call life in general.
    Virginia Woolf (1882–1941)

    Time in the hand is not control of time,
    Nor shattered fragments of an instrument
    A proof against the wind; the wind will rise,
    We can only close the shutters.
    Adrienne Rich (b. 1929)