AC Power - Reactive Power Control

Reactive Power Control

Transmission connected generators are generally required to support reactive power flow. For example on the Great Britain transmission system generators are required by the Grid Code Requirements to supply their rated power between the limits of 0.85 power factor lagging and 0.90 power factor leading at the designated terminals. The system operator will perform switching actions to maintain a secure and economical voltage profile while maintaining a reactive power balance equation:

Generator_MVARs + System_gain + Shunt_capacitors = MVAR_Demand + Reactive_losses + Shunt_reactors

The ‘System gain’ is an important source of reactive power in the above power balance equation, which is generated by the capacitive nature of the transmission network itself. By making decisive switching actions in the early morning before the demand increases, the system gain can be maximized early on, helping to secure the system for the whole day.

To balance the equation some pre-fault reactive generator use will be required. Other sources of reactive power that will also be used include shunt capacitors, shunt reactors, Static VAR Compensators and voltage control circuits.

Read more about this topic:  AC Power

Famous quotes containing the words power and/or control:

    A seashell should be the crest of England, not only because it represents a power built on the waves, but also the hard finish of the men. The Englishman is finished like a cowry or a murex.
    Ralph Waldo Emerson (1803–1882)

    Physical nature lies at our feet shackled with a hundred chains. What of the control of human nature? Do not point to the triumphs of psychiatry, social services or the war against crime. Domination of human nature can only mean the domination of every man by himself.
    Johan Huizinga (1872–1945)