Reactive Power Control
Transmission connected generators are generally required to support reactive power flow. For example on the Great Britain transmission system generators are required by the Grid Code Requirements to supply their rated power between the limits of 0.85 power factor lagging and 0.90 power factor leading at the designated terminals. The system operator will perform switching actions to maintain a secure and economical voltage profile while maintaining a reactive power balance equation:
Generator_MVARs + System_gain + Shunt_capacitors = MVAR_Demand + Reactive_losses + Shunt_reactors
The ‘System gain’ is an important source of reactive power in the above power balance equation, which is generated by the capacitive nature of the transmission network itself. By making decisive switching actions in the early morning before the demand increases, the system gain can be maximized early on, helping to secure the system for the whole day.
To balance the equation some pre-fault reactive generator use will be required. Other sources of reactive power that will also be used include shunt capacitors, shunt reactors, Static VAR Compensators and voltage control circuits.
Read more about this topic: AC Power
Famous quotes containing the words power and/or control:
“Every diminution of the public burdens arising from taxation gives to individual enterprise increased power and furnishes to all the members of our happy confederacy new motives for patriotic affection and support.”
—Andrew Jackson (17671845)
“In Vietnam, some of us lost control of our lives. I want my life back. I almost feel like Ive been missing in action for twenty-two years.”
—Wanda Sparks, U.S. nurse. As quoted in the New York Times Magazine, p. 72 (November 7, 1993)