Signal Cables - Power Cables

Power Cables

Medium and high-voltage power cables, in circuits over 2000 volts, usually have a shield layer of copper or aluminum tape or conducting polymer. If an unshielded insulated cable is in contact with earth or a grounded object, the electrostatic field around the conductor will be concentrated at the contact point, resulting in corona discharge, and eventual destruction of the insulation. As well, leakage current and capacitive current through the insulation presents a danger of electrical shock. The grounded shield equalizes electrical stress around the conductor, diverts any leakage current to ground. Be sure to apply stress relief/ cones at the shield ends, especially for cables operating at more than 2kV to earth.

Shields on power cables may be connected to earth ground at each shield end and at splices for redundancy to prevent shock even though induced current will flow in the shield. This current will produce losses and heating and will reduce the maximum current rating of the circuit. Tests show that having a bare grounding conductor adjacent to the insulated wires will conduct the fault current to earth quicker. On high current circuits the shields might be connected only at one end. On very long high-voltage circuits, the shield may be broken into several sections since a long shield run may rise to dangerous voltages during a circuit fault. However, the shock hazard of having only one end of the shield grounded must be evaluated for the risk. The maximum recommended shield potential rise is 25 volts. IEEE 422 and 525 lists the cable lengths that would limit shield potential to 25 volts for a single point ground application.

Size Conductor One Cable per Duct (ft) Three Cables per Duct (ft)
1/0 AWG 1250 4500
2/0 AWG 1110 3970
4/0 AWG 865 3000
250 kcmil 815 2730
350 kcmil 710 2260
400 kcmil 655 2100
500 kcmil 580 1870
750 kcmil 510 1500
1000 kcmil 450 -
2000 kcmil 340 -

Read more about this topic:  Signal Cables

Famous quotes containing the words power and/or cables:

    Nature has given women so much power that the law has very wisely given them little.
    Samuel Johnson (1709–1784)

    On the bare upland pasture there had spread
    O’ernight ‘twixt mullein stalks a wheel of thread
    And straining cables wet with silver dew.
    Robert Frost (1874–1963)