Reduced Pressure Zone Device - Description

Description

A RPZD is considered suitable for significant hazard applications, that is, where the consequence of backflow into the water supply would cause significant harm, although not for the highest risks, such as human waste. They are considered suitable because they prevent both backflow and back-siphonage, because of a redundant design (even with two check valves broken the device still provides protection), and because they are testable to verify correct operation.

RPZD are often chosen instead of an air gap since the head loss across the RPZ is much smaller.

The device consists of two independent check valves, plumbed in series, with a pressure monitored chamber between. The chamber is maintained at a pressure that is lower than the water supply pressure, but high enough to be useful downstream. The reduced pressure is guaranteed by a differential pressure relief valve, which automatically relieves excess pressure in the chamber by discharging to a drain. Four test cocks are installed to allow an inspector to verify proper operation of the valve with a differential pressure meter. Two gate valves (one before and one after the RPZ) are provided to allow for testing and repair.

Facilities which require constant water pressure must install two RPZs in parallel so that one device will be available to supply the facility while the other is tested or repaired.

Discharge from the relief device is an indication that either of the two check valves is 'passing' (leaking past their shutoff seats) or the relief valve itself is faulty. Some normal water use conditions may cause short episodes of discharge.

In the case of the upstream check valve passing, the differential pressure (higher supply pressure compared with the lower chamber pressure) causes any flow to occur only in one direction. A buildup of pressure in the chamber in such a case would be relieved to the drain.

In the case of the downstream check valve passing, the differential pressure relief valve prevents the possibility of the chamber pressure from exceeding the supply pressure.

It is theoretically possible that, when both valves are faulty, backflow could occur, should the reverse flow rate exceed the capacity of the relief valve.

Because certain combinations of check valve failure and/or system backpressure cause the relief valve to discharge, the device must be mounted in a location where the drain will not become flooded.

An example of where backflow would harm the water supply is the use of well washing devices inside underground sewerage pumping stations. At times untreated sewerage may contain a variety of harmful gases that will effectively break down and deteriorate concrete wells, hence well washers are utilised to spray water and wash down contaminated concrete walls of a well. All well washers are installed with RPZ Devices in case a pumping station breaks down, and the sewerage level rises above the well washer causing backflow down the water supply line.

A reduced pressure zone device is tested with a device called a differential gauge. This gauge uses hoses attached to the various test cocks of the RPZ and checks to be certain that the check valve springs as well as the relief valve spring are not fouled and are working properly. There are a variety of manufacturers of these gauges, but most utilize either a three valve or a five valve design to test the RPZ in different ways.

In the UK, New York, Texas, as well as St. Louis city and county, the RPZ valve must be tested at least every 12 months by an accredited tester.

In the UK all RPZ Valve Testers have to be WRAS Accredited

Read more about this topic:  Reduced Pressure Zone Device

Famous quotes containing the word description:

    Whose are the truly labored sentences? From the weak and flimsy periods of the politician and literary man, we are glad to turn even to the description of work, the simple record of the month’s labor in the farmer’s almanac, to restore our tone and spirits.
    Henry David Thoreau (1817–1862)

    The next Augustan age will dawn on the other side of the Atlantic. There will, perhaps, be a Thucydides at Boston, a Xenophon at New York, and, in time, a Virgil at Mexico, and a Newton at Peru. At last, some curious traveller from Lima will visit England and give a description of the ruins of St Paul’s, like the editions of Balbec and Palmyra.
    Horace Walpole (1717–1797)

    Do not require a description of the countries towards which you sail. The description does not describe them to you, and to- morrow you arrive there, and know them by inhabiting them.
    Ralph Waldo Emerson (1803–1882)