Centrifugal Fan - Centrifugal Fan Ratings

Centrifugal Fan Ratings

Ratings found in centrifugal fan performance tables and curves are based on standard air SCFM. Fan manufacturers define standard air as clean, dry air with a density of 0.075 pounds mass per cubic foot (1.2 kg/m³), with the barometric pressure at sea level of 29.92 inches of mercury (101.325 kPa) and a temperature of 70 °F (21 °C). Selecting a centrifugal fan to operate at conditions other than standard air requires adjustment to both static pressure and power.

At higher than standard elevation (sea level) and higher than standard temperature, air density is lower than standard density. Air density corrections need to be taken into account for centrifugal fans that are specified for continuous operation at higher temperatures. The centrifugal fan will displace a constant volume of air in a given system regardless of the air density.

When a centrifugal fan is specified for a given CFM and static pressure at conditions other than standard, an air density correction factor must be applied to select the proper size fan to meet the new condition. Since 200 °F (93 °C) air weighs only 80% of 70 °F (21 °C) air, the centrifugal fan will create less pressure and require less power. To get the actual pressure required at 200 °F (93 °C), the designer would have to multiply the pressure at standard conditions by an air density correction factor of 1.25 (i.e., 1.0/0.8) to get the system to operate correctly. To get the actual power at 200 °F (93 °C), the designer would have to divide the power at standard conditions by the air density correction factor.

Read more about this topic:  Centrifugal Fan

Famous quotes containing the words centrifugal and/or fan:

    Travel is like adultery: one is always tempted to be unfaithful to one’s own country. To have imagination is inevitably to be dissatisfied with where you live. There is in men, as Peter Quennell said, “a centrifugal tendency.” In our wanderlust, we are lovers looking for consummation.
    Anatole Broyard (1910–1990)

    Hard times accounted in large part for the fact that the exposition was a financial disappointment in its first year, but Sally Rand and her fan dancers accomplished what applied science had failed to do, and the exposition closed in 1934 with a net profit, which was donated to participating cultural institutions, excluding Sally Rand.
    —For the State of Illinois, U.S. public relief program (1935-1943)