Indoor Air Quality - HVAC Design

HVAC Design

Environmentally Sustainable Design concepts also include aspects related to the commercial and residential heating, ventilation and air-conditioning (HVAC) industry. Among several considerations, one of the topics to attended to is the issue of indoor air quality throughout the design and construction stages of a building's life.

One technique to reduce energy consumption while maintaining adequate air quality, is demand controlled ventilation. Instead of setting throughput at a fixed air replacement rate, carbon dioxide sensors are used to control the rate dynamically, based on the emissions of actual building occupants.

For the past several years, there have been many debates among indoor air quality specialists about the proper definition of indoor air quality and specifically what constitutes "acceptable" indoor air quality.

One way of quantitatively ensuring the health of indoor air is by the frequency of effective turnover of interior air by replacement with outside air. In the UK, for example, classrooms are required to have 2.5 outdoor air changes per hour. In halls, gym, dining, and physiotherapy spaces, the ventilation should be sufficient to limit carbon dioxide to 1,500 ppm. In the USA, and according to ASHRAE Standards, ventilation in classrooms is based on the amount of outdoor air per occupant plus the amount of outdoor air per unit of floor area, not air changes per hour. Since carbon dioxide indoors comes from occupants and outdoor air, the adequacy of ventilation per occupant is indicated by the concentration indoors minus the concentration outdoors. The value of 615 ppm above the outdoor concentration indicates approximately 15 cubic feet per minute of outdoor air per adult occupant doing sedentary office work where outdoor air contains 385 ppm, the current global average atmospheric CO2 concentration. In classrooms, the requirements in the ASHRAE standard 62.1, Ventilation for Acceptable Indoor Air Quality, would typically result in about 3 air changes per hour, depending on the occupant density. Of course the occupants aren't the only source of pollutants, so outdoor air ventilation may need to be higher when unusual or strong sources of pollution exist indoors. When outdoor air is polluted, then bringing in more outdoor air can actually worsen the overall quality of the indoor air and exacerbate some occupant symptoms related to outdoor air pollution. Generally, outdoor country air is better than indoor city air. Exhaust gas leakages can occur from furnace metal exhaust pipes that lead to the chimney when there are leaks in the pipe and the pipe gas flow area diameter has been reduced.

The use of air filters can trap some of the air pollutants. The Department of Energy's Energy Efficiency and Renewable Energy section wrote " Filtration should have a Minimum Efficiency Reporting Value (MERV) of 13 as determined by ASHRAE 52.2-1999." Air filters are used to reduce the amount of dust that reaches the wet coils. Dust can serve as food to grow molds on the wet coils and ducts and can reduce the efficiency of the coils.

Moisture management and humidity control requires operating HVAC systems as designed. Moisture management and humidity control may conflict with efforts to try to optimize the operation to conserve energy. For example, Moisture management and humidity control requires systems to be set to supply Make Up Air at lower temperatures (design levels), instead of the higher temperatures sometimes used to conserve energy in cooling-dominated climate conditions. However, for most of the US and many parts of Europe and Japan, during the majority of hours of the year, outdoor air temperatures are cool enough that the air does not need further cooling to provide thermal comfort indoors. However, high humidity outdoors creates the need for careful attention to humidity levels indoors. High humidities give rise to mold growth and moisture indoors is associated with a higher prevalence of occupant respiratory problems.

The "dew point temperature" is an absolute measure of the moisture in air. Some facilities are being designed with the design dew points in the lower 50's °F, and some in the upper and lower 40's °F. Some facilities are being designed using desiccant wheels with gas fired heater to dry out the wheel enough to get the required dew points. On those systems, after the moisture is removed from the make up air, a cooling coil is used to lower the temperature to the desired level.

Commercial buildings, and sometimes residential, are often kept under slightly positive air pressure relative to the outdoors to reduce infiltration. Limiting infiltration helps with moisture management and humidity control.

Dilution of indoor pollutants with outdoor air is effective to the extent that outdoor air is free of harmful pollutants. Ozone in outdoor air occurs indoors at reduced concentrations because ozone is highly reactive with many chemicals found indoors. The products of the reactions between ozone and many common indoor pollutants include organic compounds that may be more odorous, irritating, or toxic than those from which they are formed. These products of ozone chemistry include formaldehyde, higher molecular weight aldehydes, acidic aerosols, and fine and ultrafine particles, among others. The higher the outdoor ventilation rate, the higher the indoor ozone concentration and the more likely the reactions will occur, but even at low levels, the reactions will take place. This suggests that ozone should be removed from ventilation air, especially in areas where outdoor ozone levels are frequently high. Recent research has shown that mortality and morbidity increase in the general population during periods of higher outdoor ozone and that the threshold for this effect is around 20 parts per billion (ppb).

Read more about this topic:  Indoor Air Quality

Famous quotes containing the word design:

    I begin with a design for a hearse.
    For Christ’s sake not black—
    nor white either—and not polished!
    Let it be weathered—like a farm wagon—
    William Carlos Williams (1883–1963)