Modes
There are two main operational modes of HART instruments: analog/digital mode, and multidrop mode.
In point-to-point mode (analog/digital) the digital signals are overlaid on the 4-20 mA loop current. Both the 4-20 mA current and the digital signal are valid output values from the instrument. The polling address of the instrument is set to "0". Only one instrument can be put on each instrument cable signal pair. One signal, generally specified by the user, is specified to be the 4-20 mA signal. Other signals are sent digitally on top of the 4-20 mA signal. For example, pressure can be sent as 4-20 mA, representing a range of pressures, and temperature can be sent digitally over the same wires.
In multidrop mode (digital) only the digital signals are used. The analog loop current is fixed at 4 mA. In multidrop mode it is possible to have more than one instruments on one signal cable. HART revisions 3 through 5 allowed polling addresses of the instruments to be in the range 1-15. HART 6 and later allowed address up to 63. Each meter needs to have a unique address.
Read more about this topic: Highway Addressable Remote Transducer Protocol
Famous quotes containing the word modes:
“Sight and all the other senses are only modes of touch.”
—Samuel Butler (18351902)
“my brain
Worked with a dim and undetermined sense
Of unknown modes of being; oer my thoughts
There hung a darkness, call it solitude
Or blank desertion.”
—William Wordsworth (17701850)
“The essence of belief is the establishment of a habit; and different beliefs are distinguished by the different modes of action to which they give rise.”
—Charles Sanders Peirce (18391914)