Modes
There are two main operational modes of HART instruments: analog/digital mode, and multidrop mode.
In point-to-point mode (analog/digital) the digital signals are overlaid on the 4-20 mA loop current. Both the 4-20 mA current and the digital signal are valid output values from the instrument. The polling address of the instrument is set to "0". Only one instrument can be put on each instrument cable signal pair. One signal, generally specified by the user, is specified to be the 4-20 mA signal. Other signals are sent digitally on top of the 4-20 mA signal. For example, pressure can be sent as 4-20 mA, representing a range of pressures, and temperature can be sent digitally over the same wires.
In multidrop mode (digital) only the digital signals are used. The analog loop current is fixed at 4 mA. In multidrop mode it is possible to have more than one instruments on one signal cable. HART revisions 3 through 5 allowed polling addresses of the instruments to be in the range 1-15. HART 6 and later allowed address up to 63. Each meter needs to have a unique address.
Read more about this topic: Highway Addressable Remote Transducer Protocol
Famous quotes containing the word modes:
“Heaven is large, and affords space for all modes of love and fortitude. Why should we be busybodies and superserviceable?”
—Ralph Waldo Emerson (18031882)
“I cannot beat off
Invincible modes of the sea, hearing:
Be a man my son by God.
He turned again
To the purring jet yellowing the murder story,
Deaf to the pathos circling in the air.”
—Allen Tate (18991979)
“Of the modes of persuasion furnished by the spoken word there are three kinds. The first kind depends on the personal character of the speaker; the second on putting the audience into a certain frame of mind; the third on the proof, provided by the words of the speech itself.”
—Aristotle (384323 B.C.)