Highway Addressable Remote Transducer Protocol - Modes

Modes

There are two main operational modes of HART instruments: analog/digital mode, and multidrop mode.

In point-to-point mode (analog/digital) the digital signals are overlaid on the 4-20 mA loop current. Both the 4-20 mA current and the digital signal are valid output values from the instrument. The polling address of the instrument is set to "0". Only one instrument can be put on each instrument cable signal pair. One signal, generally specified by the user, is specified to be the 4-20 mA signal. Other signals are sent digitally on top of the 4-20 mA signal. For example, pressure can be sent as 4-20 mA, representing a range of pressures, and temperature can be sent digitally over the same wires.

In multidrop mode (digital) only the digital signals are used. The analog loop current is fixed at 4 mA. In multidrop mode it is possible to have more than one instruments on one signal cable. HART revisions 3 through 5 allowed polling addresses of the instruments to be in the range 1-15. HART 6 and later allowed address up to 63. Each meter needs to have a unique address.

Read more about this topic:  Highway Addressable Remote Transducer Protocol

Famous quotes containing the word modes:

    Sight and all the other senses are only modes of touch.
    Samuel Butler (1835–1902)

    The human condition is such that pain and effort are not just symptoms which can be removed without changing life itself; they are the modes in which life itself, together with the necessity to which it is bound, makes itself felt. For mortals, the “easy life of the gods” would be a lifeless life.
    Hannah Arendt (1906–1975)

    In the final analysis, “style” is art. And art is nothing more or less than various modes of stylized, dehumanized representation.
    Susan Sontag (b. 1933)