Stand-alone Power Systems
Cabling for extra-low voltage systems, such as in remote-area power systems (RAPS), is designed to minimise energy losses while maximising safety. Lower voltages require a higher current for the same power. The higher current results in greater resistive losses in the cabling. Cable sizing must therefore consider maximum demand, voltage drop over the cable, and current-carrying capacity. Voltage drop is usually the main factor considered, but current-carrying capacity is as important when considering short, high-current runs such as between a battery bank and inverter.
Arcing is a risk in DC ELV systems, and some fuse types which can cause undesired arcing include semi-enclosed, rewireable and automotive fuse types. Instead high rupturing capacity fuses and appropriately rated circuit breakers are the recommended type for RAPS. Cable termination and connections must be done properly to avoid arcing also, and soldering is not recommended.
Read more about this topic: Extra-low Voltage
Famous quotes containing the words power and/or systems:
“I spoke at a womans club in Philadelphia yesterday and a young lady said to me afterwards, Well, that sounds very nice, but dont you think it is better to be the power behind the throne? I answered that I had not had much experience with thrones, but a woman who has been on a throne, and who is now behind it, seems to prefer to be on the throne.”