Earth Potential Rise - Step, Touch, and Mesh Potentials

Step, Touch, and Mesh Potentials

"Step potential" is the voltage between the feet of a person standing near an energized grounded object. It is equal to the difference in voltage, given by the voltage distribution curve, between two points at different distances from the "electrode". A person could be at risk of injury during a fault simply by standing near the grounding point.

"Touch potential" is the voltage between the energized object and the feet of a person in contact with the object. It is equal to the difference in voltage between the object and a point some distance away. The touch potential could be nearly the full voltage across the grounded object if that object is grounded at a point remote from the place where the person is in contact with it. For example, a crane that was grounded to the system neutral and that contacted an energized line would expose any person in contact with the crane or its uninsulated load line to a touch potential nearly equal to the full fault voltage.

"Mesh potential" is a factor calculated when a grid of grounding conductors is installed. Mesh potential is the difference between the metallic object connected to the grid, and the potential of the soil within the grid. It is significant because a person may be standing inside the grid at a point with a large potential relative to the grid itself.

Read more about this topic:  Earth Potential Rise